Nova 180 kW DC fast EV charger









A 180 kW DC fast EV charger with two CCS2 guns, ARAI certified. Start by RFID, UPI or app, on OCPP 1.6.
Nova 180 is a 180 kW DC fast EV charger made by Zevpoint for commercial sites in India, with CCS2 guns, a 2-year warranty and pan-India service. Price: Rs. 999,000.00 ex-factory, plus 5% GST; GST and freight are added at checkout. Dispatched in 2–3 working days. Zevpoint plans the site and sends a proposal within 24 hours.
- 2 × CCS2 guns
- OCPP 1.6
- RFID, UPI & App
- ARAI certified
A 180 kW DC charger for busy highway and fleet sites that charges two vehicles at once, run from one dashboard.
- 7- or 10-inch screen: Touch screen, in the size you choose.
- 2 × CCS2 guns, 5 m: Charges two vehicles at the same time.
- RFID, QR or password: Drivers start a session their way.
- UPI and card: Drivers pay through the Zevpoint app.
- Real-time monitoring: Charger status, availability and faults.
- Session management: Every session and the energy it used.
- Pricing and revenue: Set tariffs and track what you earn.
- Remote management: Manage chargers from anywhere.
- 10+ protections: Over-current, surge, leakage, ground fault, reverse polarity and more.
- Insulation monitoring: Watches the high-voltage side all the time.
- IP54 · IK10: Dust, splash and impact resistant.
- ARAI · CE certified: Tested to Indian and international standards.
Which one is right for you?
- Navigator 30 (30 kW): Offices, dealerships, fleet depots and housing societies.
- Nova 60 (60 kW): Charging hubs, highway stops, fleet depots and societies.
- Nova 120 (120 kW): Highway stations, logistics hubs and large societies.
- Nova 180 (180 kW): Busy highway stations and logistics hubs, buses and trucks too.
- Nova 240 (240 kW): Highway corridors, heavy fleets and large public stations.
Nova 180 specifications
- Output: Up to 180 kW DC, two vehicles at the same time
- Guns: 2 × CCS2, 5 m cables
- Input supply: Three phase, 380–415 V AC, 50 Hz
- Sanctioned load: About 200 kVA, as sanctioned by your DISCOM
- Input current: 270–345 A
- Output voltage: 150–1000 V DC
- Efficiency: Above 95.5%
- Protection rating: IP54, dust and splash resistant
- Impact rating: IK10
- Safety: Emergency stop, over-current, short-circuit, over-temperature, leakage, surge, under- and over-voltage, ground fault, reverse polarity, insulation monitoring, charge cable temperature detection
- Certifications: ARAI, CE
- Compliance: IEC 61851-1, IEC 61851-21-2
- Suits: Any car, bus or truck with a CCS2 socket
- Display: 7-inch or 10-inch touch screen, your choice
- Start a session: RFID, OCPP 1.6, password or QR code
- Payment: UPI and card, through the Zevpoint app
- Network: OCPP 1.6 over Wi-Fi or 4G
- Cooling: Air
- Housing: Stainless steel
- Operating temperature: -25°C to +70°C
- Warranty: 2-year warranty
What your site needs for Nova 180
- Power supply: About 200 kVA, 3-phase 415 V — Sanctioned supply, as approved by your DISCOM.
- Supply cable: 185 sq mm 4-core armoured copper — Or 300 sq mm 4-core armoured aluminium.
- Upstream protection: 400 A MCCB/ACB + DC isolator — At the supply end, for the charger only.
- Earthing: 4 earth pits, under 1 Ω — With equipotential bonding, tested before switch-on.
- Civil work: 1.5 × 1.2 m RCC plinth — With a canopy over the charger.
- Connectivity: Wi-Fi or 4G SIM — Keeps the charger online for OCPP.
How does buying a DC charger work?
Book a site study. An engineer visits your plot, and you get the layout, single-line diagram, bill of quantities and payback for your site, with a full proposal in 24 hours.
One team then supplies, installs and commissions the charger. How plan and build works
What does my site need?
A three-phase 415 V connection with enough sanctioned load, an armoured supply cable, upstream protection, earth pits and an RCC plinth. The figures for Nova 180 are under “What your site needs” on this page.
Do I need a franchise to run it?
No. You own the charger, set your own tariffs and track what you earn. It runs on OCPP 1.6, so it can connect to a charging network.
How do drivers start a session and pay?
They start by RFID card, QR code or password, and pay by UPI or card through the Zevpoint app.
How do I manage it?
From anywhere: you see the charger’s status and faults live, every session and the energy it used, and your revenue.
What warranty and service come with it?
A 2-year warranty, with service across India.
Support: support@zevpoint.com · +91 9779750538 · Monday to Saturday, 10 AM to 6 PM.
How soon will I get it?
It is dispatched in 2–3 working days.
Can I return it?
DC chargers are not returnable. That is why we plan the site with you before you order. Full return policy
Nova 180 is an ARAI-certified 180 kW DC fast charger with two CCS2 guns that charge two vehicles at the same time. It charges cars, buses and trucks, for highway stations, logistics hubs, fleet depots and large housing societies.
It connects to a charging network over OCPP 1.6, starts sessions by RFID, password or QR code, and takes UPI or card payment through the Zevpoint app.
Specifications
- Output: Up to 180 kW DC, two vehicles at the same time
- Guns: 2 x CCS2, 5 m cables
- Suits: Any car, bus or truck with a CCS2 socket
- Input supply: Three phase, 380-415V AC, 50Hz
- Sanctioned load: About 200 kVA, as sanctioned by your DISCOM
- Input current: 270-345A
- Output voltage: 150-1000V DC
- Efficiency: Above 95.5%
- Display: 7-inch or 10-inch touch screen, your choice
- Start a session: RFID, OCPP 1.6, password or QR code
- Payment: UPI and card, through the Zevpoint app
- Protection rating: IP54, dust and splash resistant
- Impact rating: IK10
- Cooling: Air
- Safety: Emergency stop, over-current, short-circuit, over-temperature, leakage, surge, under- and over-voltage, ground fault, reverse polarity, insulation monitoring, charge cable temperature detection
- Operating temperature: -25°C to +70°C
- Warranty: 2 years on-site, with 48-hour priority service
Site readiness
- Power supply: 3-phase 415V AC input, about 200 kVA, sanctioned supply as per DISCOM
- Supply cable: 185 sq mm 4-core armoured copper, or 300 sq mm 4-core armoured aluminium
- Upstream protection: 400A MCCB/ACB + DC isolator
- Earthing: 4 earth pits, <1 ohm + equipotential bonding
- Civil work: 1.5m x 1.2m RCC plinth + canopy
- Connectivity: Broadband or 4G SIM at site for OCPP